PRICES include / exclude VAT
Homepage>BS Standards>29 ELECTRICAL ENGINEERING>29.120 Electrical accessories>29.120.99 Other electrical accessories>BS EN 61095:2009 Electromechanical contactors for household and similar purposes
Sponsored link
immediate downloadReleased: 2009-05-31
BS EN 61095:2009 Electromechanical contactors for household and similar purposes

BS EN 61095:2009

Electromechanical contactors for household and similar purposes

Format
Availability
Price and currency
English Secure PDF
Immediate download
399.30 EUR
You can read the standard for 1 hour. More information in the category: E-reading
Reading the standard
for 1 hour
39.93 EUR
You can read the standard for 24 hours. More information in the category: E-reading
Reading the standard
for 24 hours
119.79 EUR
English Hardcopy
In stock
399.30 EUR
Standard number:BS EN 61095:2009
Pages:132
Released:2009-05-31
ISBN:978 0 580 67852 3
Status:Standard
DESCRIPTION

BS EN 61095:2009


This standard BS EN 61095:2009 Electromechanical contactors for household and similar purposes is classified in these ICS categories:
  • 29.200 Rectifiers. Converters. Stabilized power supply
  • 29.120.99 Other electrical accessories
  • 29.130.20 Low voltage switchgear and controlgear
IEC 61095:2009 applies to electromechanical air break contactors for household and similar purposes provided with main contacts intended to be connected to circuits the rated voltage of which does not exceed 440 V a.c. (between phases) with rated operational currents less than or equal to 63 A for utilization category AC-7a and 32 A for utilization categories AC-7b and AC-7c, and rated conditional short-circuit current less than or equal to 6 kA. This second edition cancels and replaces the first edition published in 1992 and its Amendment 1 (2000), and constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
- deletion of switching overvoltages requirements,
- addition of a new utilization category AC-7c: switching of compensated electric discharge lamp control,
- measuring of U imp required, but the marking is not required if U imp equal to 4 kV,
- improvement regarding marking concerning direction of movement,
- improvement of dielectric properties,
- test of resistance to humidity referred to IEC 60068-2-78 instead of IEC 60068-2-3,
- amendment to Table B.1 regarding test sequences,
- deletion of Table F.2 regarding the correspondence between the nominal voltage of the supply system and the contactor rated impulse withstand voltage,
- addition of a new Annex H (normative): degrees of protection of enclosed contactor,
- addition of a new Annex I (normative): requirements and tests for equipment with protective separation.