District cooling pipes - Bonded single pipe systems for directly buried cold water networks - Part 2: Factory made fitting assemblies of steel or plastic service pipe, polyurethane thermal insulation and a casing of polyethylene
Format
Availability
Price and currency
English Hardcopy
In stock
93.33 USD
FREE Shipping
Number of Standard:
CSN EN 17415-2
Category:
383386
Pages:
40
Released:
01.12.2021
Catalog number:
513449
DESCRIPTION
CSN EN 17415-2
CSN EN 17415-2 (38 3386) This document specifies requirements, design and test methods for factory made thermally insulated bonded fitting assemblies for directly buried district cooling distribution systems, comprising a service fitting from DN 15 to DN 1200, rigid polyurethane foam insulation and a casing of polyethylene. The fitting assembly can also include the following additional elements: measuring wires, spacers and diffusion barriers. This document covers the following fitting assemblies: bend, tee, reducer, cap and anchor. This document applies only to insulated fitting assemblies, for continuous operation with water at various temperatures (1 to 30) °C and a maximum operation pressure of 25 bar. The design is based on an expected service life with continuous operation of a minimum 50 years. NOTE - An expected service life of 50 years presupposes that treated water is used. Original English text of CSN EN Standard. The price of the Standard included all amendments and correcturs.